CΓ©dula de Cables
Listado de cables/circuitos as-built β 110 registros.
| # | CIRCUIT ID | FROM (Origin) | TO (Destination) | CONNECTION TYPE | CABLE ID / WIRE # | CABLE SPEC | ROUTE | PROTECTION | TERMINAL BLOCKS | STATUS | EVIDENCE SOURCE | FIELD NOTES | PRIORITY | SHEET SOURCE |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | SU-001 | Houston Utility Service (UNKNOWN) | Main MCC (NOT DOCUMENTED) | PWR-AC | N/A | PENDING β service kVA unknown | Service entrance β Houston facility | MCC main breaker ~1200A | N/A | TO BE VERIFIED | P1-001/P1-002 Gap | CRITICAL: Entire line blocked until utility service data and MCC engineering completed | P1 | STARTUP |
| 2 | SU-002 | MCC Main Bus 480V | P-01 Main Panel β CB-001 (ABB D30 30A, tag 00100CB) | PWR-AC | N/A | 3/0 AWG+ XHHW-2 (size per final MCC design) | MCC to P-01 top entry β cable tray | CB-001 30A β ALERT: UNDERSIZED for 1,335HP | L1/L2/L3 at CB-001 line side 1-3-5 | WARNING | IMG_1360; CB-001 label photo | CB-001 confirmed at 30A only. MCC not in any evidence source. | P1 | STARTUP |
| 3 | SU-003 | P-01 Bus 480V (load side CB-001) | Control Transformer ACME (XFMR-CTRL) Primary H1-H4 | PWR-AC | N/A | #10 AWG THHN internal | Internal panel wiring β top zone | Panel internal breaker / fuse | H1-H4 primary taps | CONFIRMED | IMG_4280; IMG_1943 | Transformer secondary X1-X4 = 110/120VAC for solenoid circuits. VERIFY tap setting for Houston voltage. | P2 | STARTUP |
| 4 | SU-004 | P-01 Bus 480V | P-04 PowerFlex 20P #1 Input L1/L2/L3 | PWR-AC | DC-PWR-01 | 2/0 AWG XHHW-2 (336.6A input) | P-01 to P-04 β cable tray | Dedicated breaker (size PENDING MCC) | L1/L2/L3 drive input terminals | CONFIRMED | P2P DC-PWR-01; Drive nameplate 20P41AD412RA0NNN SV3RC1KR; IMG_1555 | Input: 460V/336.6A 3PH. Output: 500VDC/412A REGEN. FW V7.002. | P1 | STARTUP |
| 5 | SU-005 | P-01 Bus 480V | P-04 PowerFlex 20P #2 Input L1/L2/L3 | PWR-AC | DC-PWR-02 | 2/0 AWG XHHW-2 (336.6A input) | P-01 to P-04 β cable tray | Dedicated breaker (size PENDING MCC) | L1/L2/L3 drive input terminals | CONFIRMED | P2P DC-PWR-02; Drive nameplate E47E0025 | FW V5.005 vs V7.002 on #1 β firmware mismatch must be resolved. | P1 | STARTUP |
| 6 | SU-006 | P-04 PF20P #1 Armature Output A+/A- | MTR-01 β UNICO DC S/N 35748 β Armature A1/A2 | PWR-DC | DC-MTR-01 (cable E315270) | 4/0 AWG XHHW-2 (360A DC armature) | P-04 β conduit β pit β JBOX-01 β JBOX-02 TB70-72 β Motor | Drive integral protection + Shawmut fuses | A+/A- at drive; A1/A2 at motor | CONFIRMED | P2P DC-MTR-01; IMG_1948 (cable label E315270); Motor S/N 35748 | DO NOT invert polarity A1/A2. 500VDC, 360A. REGEN drive. | P1 | STARTUP |
| 7 | SU-007 | P-04 PF20P #2 Armature Output A+/A- | MTR-02 β UNICO DC S/N 35749 β Armature A1/A2 | PWR-DC | DC-MTR-02 | 4/0 AWG XHHW-2 (360A DC armature) | P-04 β conduit β pit β JBOX-01 β JBOX-02 TB70-72 β Motor | Drive integral protection | A+/A- at drive; A1/A2 at motor | CONFIRMED | P2P DC-MTR-02; MER-016/017; S/N 35749 | Parallel field mode: 150V/5.5A. | P1 | STARTUP |
| 8 | SU-008 | P-04 PF20P #1 Field Output F+/F- | MTR-01 UNICO S/N 35748 Shunt Field | PWR-DC | DC-FLD-01 | #10 AWG shielded (5.5A field) | Bundled with armature conduit | Drive field protection | F+/F- drive; Field terminals motor | CONFIRMED | P2P DC-FLD-01; Motor nameplate: parallel mode 150V/5.5A/11.3 ohm | Measure field resistance (11.3 ohm) before energizing. | P1 | STARTUP |
| 9 | SU-009 | P-04 PF20P #2 Field Output F+/F- | MTR-02 UNICO S/N 35749 Shunt Field | PWR-DC | DC-FLD-02 | #10 AWG shielded (5.5A field) | Bundled with armature conduit | Drive field protection | F+/F- drive; Field terminals motor | CONFIRMED | P2P DC-FLD-02; Motor nameplate S/N 35749 | Parallel mode: 150V/5.5A. | P1 | STARTUP |
| 10 | SU-010 | P-01 Bus 480V | P-03 Parker AC890 Rack (325HP total) β Input through TCI reactors | PWR-AC | AC890-PWR-RACK | 250A+ estimated (architecture PENDING) | P-01 to P-03 β cable tray through TCI KDRH3L/KDRF2L reactors | Rack input breaker PENDING confirmation | TB6 per drive; R/S/T at each AC890 | PARTIAL | P2P AC890-PWR-RACK; IMG_1969 (TCI reactor) | DC bus architecture (shared vs individual) NOT confirmed. | P1 | STARTUP |
| 11 | SU-011 | P-01 Bus 480V | Parker AC890PX Input R/S/T (Flattener 300HP) | PWR-AC | AC-PWR-PX | ~250 MCM estimated (FLA not confirmed) | P-01 to AC890PX standalone cabinet β cable tray | Dedicated breaker (size PENDING) | R/S/T drive input | PARTIAL | P2P AC-PWR-PX; AC890PX Cat# 890PX/4/6420/B/01/A | FLA not confirmed from Parker manual. | P1 | STARTUP |
| 12 | SU-012 | AC890PX Output U/V/W | MTR-300 β UNICO/Reliance 300HP Flattener β T1/T2/T3 | PWR-AC | AC-MTR-300 | 350 MCM per phase (355A FLA @ 84Hz) | AC890PX β conduit β pit β Motor T1/T2/T3 | Drive integral IGBT protection | U/V/W at drive; T1/T2/T3 at motor | CONFIRMED | P2P AC-MTR-300; Nameplate S/N 61812I; IMG_1766-1767 | BASE FREQUENCY = 84Hz NOT 60Hz. DPFV blower MANDATORY. | P1 | STARTUP |
| 13 | SU-013 | P-01 β Banner ES-UA-5A K1/K2 Safety Outputs | Each AC890 Roll #1-#6 + AC890PX β STO A/STO B connector X11 | SAFETY | AC890-STO | #16 AWG 2C shielded per drive (SIL-rated) | P-01 dedicated safety conduit β P-03 VFD rack | Banner ES-UA-5A dual-channel β SIL 2 | S31/S32/S34 at Banner; X11 STO A/STO B | CONFIRMED | P2P AC890-STO; MER-060; ADDENDUM Lote3 IMG_2157 | FIRST function test before any motor run. All 7 drives. | P1 | STARTUP |
| 14 | SU-014 | P-01 β Phoenix QUINT PS (24VDC/30A) | P-01 24VDC Control Bus β field I/O modules | CTRL | D1-24V / D1COM | Internal bus wiring | DIN rail internal to P-01 | 1489-A 3A breaker (confirmed) | D1-24V, D1COM labels confirmed (IMG_1745) | CONFIRMED | MER-055; P2P wire numbers D1-24V, D1COM; IMG_1745 | Primary 24VDC backbone. Verify output voltage at receiving. | P1 | STARTUP |
| 15 | SU-015 | P-01 Hirschmann SPIDER STX | ControlLogix 5561 / L32E / L24ER / 1794-AENT / PanelView / VFS4-AENT / DirectLOGIC | ENET | ENET-01 to 07 | Cat5e/6 STP RJ45 (Γ7 cables) | Internal panel + panel to P-04 and P-05 console | Switch internal protection | RJ45 ports at Hirschmann; Ethernet ports at each device | PARTIAL | P2P ENET-01 to 07; MER-053; IMG_4245 | Port assignments not documented. IPs not confirmed except DL-205=192.168.84.101. | P1 | STARTUP |
| 16 | DC-PWR-01 | MCC Bus 480V | P-04 PF20P #1 L1/L2/L3 | PWR-AC | DC-PWR-01 | 2/0 AWG XHHW-2 | MCC β cable tray β P-04 | Dedicated breaker ~400A (pending MCC) | L1/L2/L3 drive input | CONFIRMED | P2P DC-PWR-01; Nameplate; IMG_1555 | 336.6A input FLA. | P1 | POWER |
| 17 | DC-PWR-02 | MCC Bus 480V | P-04 PF20P #2 L1/L2/L3 | PWR-AC | DC-PWR-02 | 2/0 AWG XHHW-2 | MCC β cable tray β P-04 | Dedicated breaker ~400A (pending) | L1/L2/L3 drive input | CONFIRMED | P2P DC-PWR-02; Nameplate E47E0025 | FW V5.005 mismatch with #1 V7.002. | P1 | POWER |
| 18 | DC-PWR-03 | MCC Bus 480V | P-04 PF20P #3 DECOILER L1/L2/L3 | PWR-AC | DECO-PWR | PENDING β motor HP unknown | MCC β cable tray β P-04 | PENDING β breaker cannot be sized | L1/L2/L3 drive input | TO BE VERIFIED | P2P DECO-PWR; Checklist D3 | Motor HP/V/FLA COMPLETELY UNKNOWN. | P1 | POWER |
| 19 | DC-MTR-01 | P-04 PF20P #1 A+/A- | MTR-01 UNICO S/N 35748 Armature A1/A2 | PWR-DC | E315270 (confirmed label) | 4/0 AWG XHHW-2 (360A DC) | P-04 β conduit β pit β JBOX-01 β JBOX-02 TB70-72 β motor | Drive integral + Shawmut CC 330A | A+/A- drive; A1/A2 motor | CONFIRMED | IMG_1948 cable label E315270; P2P DC-MTR-01; Motor S/N 35748 | Verify A1=+ A2=β polarity. | P1 | POWER |
| 20 | DC-MTR-02 | P-04 PF20P #2 A+/A- | MTR-02 UNICO S/N 35749 Armature A1/A2 | PWR-DC | DC-MTR-02 | 4/0 AWG XHHW-2 (360A DC) | P-04 β conduit β pit β JBOX-01 β JBOX-02 TB70-72 β motor | Drive integral | A+/A- drive; A1/A2 motor | CONFIRMED | P2P DC-MTR-02; Motor S/N 35749 | Same route as DC-MTR-01 (bundled conduit). | P1 | POWER |
| 21 | DC-FLD-01 | P-04 PF20P #1 F+/F- | MTR-01 Shunt Field F+/F- | PWR-DC | DC-FLD-01 | #10 AWG shielded (5.5A, 150V) | Bundled with armature conduit | Drive field regulator | F+/F- at drive; field terminals at motor | CONFIRMED | P2P DC-FLD-01; Motor nameplate: parallel 150V/5.5A/11.3 ohm | Series mode: 300V/2A. | P1 | POWER |
| 22 | DC-FLD-02 | P-04 PF20P #2 F+/F- | MTR-02 Shunt Field F+/F- | PWR-DC | DC-FLD-02 | #10 AWG shielded (5.5A, 150V) | Bundled with armature conduit | Drive field regulator | F+/F- drive; field terminals motor | CONFIRMED | P2P DC-FLD-02; Motor S/N 35749 | Same specs as DC-FLD-01. | P1 | POWER |
| 23 | DC-BLWR-01 | P-01 or P-04 240/480V distribution | Blower Motor P/N 303-063 on MTR-01 | PWR-AC | DC-BLWR-01 | #14 AWG 3C+GND (~3A FLA estimated) | Panel β conduit β blower terminal box at motor | Branch breaker ~10A | Blower terminal box | PARTIAL | P2P DC-BLWR-01; Motor nameplate: blower 303-063, 240/480V 1HP 3450RPM | DPFV blower MUST be running before MTR-01. | P1 | POWER |
| 24 | DC-BLWR-02 | P-01 or P-04 240/480V distribution | Blower Motor P/N 303-063 on MTR-02 | PWR-AC | DC-BLWR-02 | #14 AWG 3C+GND | Panel β conduit β blower terminal box at motor | Branch breaker ~10A | Blower terminal box | PARTIAL | P2P DC-BLWR-02; Motor nameplate: blower 303-063 | Same as DC-BLWR-01. | P1 | POWER |
| 25 | AC-PWR-PX | MCC Bus 480V | Parker AC890PX Input R/S/T (Flattener) | PWR-AC | AC-PWR-PX | ~250 MCM (FLA pending) | MCC β cable tray β AC890PX cabinet | Dedicated breaker (size PENDING) | R/S/T drive input | PARTIAL | P2P AC-PWR-PX; AC890PX Cat# label; MER-002 | DC bus architecture unknown. Requires Parker documentation. | P1 | POWER |
| 26 | AC-MTR-300 | AC890PX Output U/V/W | MTR-300 UNICO/Reliance 300HP T1/T2/T3 | PWR-AC | AC-MTR-300 | 350 MCM per phase (355A FLA) | AC890PX β conduit β pit β motor terminal box | Drive IGBT; motor OL relay (if external) | U/V/W drive; T1/T2/T3 motor | CONFIRMED | P2P AC-MTR-300; Nameplate S/N 61812I; IMG_1766 | RATED 84Hz NOT 60Hz. DPFV blower mandatory. | P1 | POWER |
| 27 | ROLL-01 | P-03 AC890 Roll#1 (Node1 Tag2301) U/V/W | Roll Motor #1 T1/T2/T3 (75HP) | PWR-AC | ROLL-01 Tag 2301 | #4 AWG XHHW-2 (~96A FLA est.) | P-03 VFD rack β conduit β roll motor | Drive integral protection | U/V/W drive; T1/T2/T3 motor | PARTIAL | P2P ROLL-01; MER-005; IMG_1960 | Motor nameplate PENDING. HP=75 from drive tag only. | P1 | POWER |
| 28 | ROLL-02 | P-03 AC890 Roll#2 (Node4 Tag2401) U/V/W + TCI KDRH3L 124A | Roll Motor #2 T1/T2/T3 (100HP) | PWR-AC | ROLL-02 Tag 2401 | #2 AWG XHHW-2 (~124A FLA) | P-03 β TCI KDRH3L 124A reactor β conduit β motor | Drive integral; TCI reactor | U/V/W drive; T1/T2/T3 motor | CONFIRMED | P2P ROLL-02; MER-006; IMG_1962/1969 (reactor) | Highest HP roll. Reactor assignment confirmed. | P1 | POWER |
| 29 | ROLL-03 | P-03 AC890 Roll#3 (Node5 Tag2501) U/V/W + TCI KDRF2L ~96A | Roll Motor #3 T1/T2/T3 (75HP) | PWR-AC | ROLL-03 Tag 2501 | #4 AWG XHHW-2 (~96A FLA est.) | P-03 β TCI KDRF2L ~96A β conduit β motor | Drive integral; KDRF2L reactor | U/V/W drive; T1/T2/T3 motor | PARTIAL | P2P ROLL-03; MER-007/012; IMG_1963-64 | KDRF2L reactor drive assignment TBD. | P2 | POWER |
| 30 | ROLL-04 | P-03 AC890 Roll#4 (Node6 Tag~2601) U/V/W | Roll Motor #4 T1/T2/T3 (25HP) | PWR-AC | ~2601 | #10 AWG XHHW-2 (~34A FLA est.) | P-03 β conduit β motor | Drive integral | U/V/W drive; T1/T2/T3 motor | PARTIAL | P2P ROLL-04; MER-008 | Tag 2601 not fully confirmed. Motor nameplate PENDING. | P2 | POWER |
| 31 | ROLL-05 | P-03 AC890 Roll#5 (Node7 Tag2701) U/V/W | Roll Motor #5 T1/T2/T3 (25HP) | PWR-AC | 2701 | #10 AWG XHHW-2 (~34A FLA est.) | P-03 β conduit β motor | Drive integral | U/V/W drive; T1/T2/T3 motor | CONFIRMED | P2P ROLL-05; MER-009; IMG_1977; Tag 2701 label | 903/FA option card visible. Motor nameplate PENDING. | P2 | POWER |
| 32 | ROLL-06 | P-03 AC890 Roll#6 (Node8 Tag2801) U/V/W | Roll Motor #6 T1/T2/T3 (25HP) | PWR-AC | 2801 / wires 2805-2807 | #10 AWG XHHW-2 (~34A FLA est.) | P-03 β conduit β motor | Drive integral | U/V/W drive; T1/T2/T3 motor; wires 2801/2805-07 | CONFIRMED | P2P ROLL-06; IMG_1977 (wire labels); IMG_1948 | Label has '(?)' β verify Roll#6 identity at Houston. | P2 | POWER |
| 33 | PWR-MARA100 | UNKNOWN β no MCC breaker documented | Marathon 100HP Inv.Duty 460V 1190/1780RPM | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Drive/starter assignment, cable route, protection all UNKNOWN. | P1 | POWER |
| 34 | PWR-MARA60 | UNKNOWN | Marathon 60HP Inv.Duty 460V 1178/1780RPM | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Same status. | P1 | POWER |
| 35 | PWR-WEG125 | UNKNOWN | WEG 125HP 460V 1780RPM | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Same status. | P1 | POWER |
| 36 | PWR-HPU1 | UNKNOWN | HPU Motor #1 (M-10) β nameplate unreadable | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Checklist M-10 | HPU may start automatically. Ensure LOTO. | P1 | POWER |
| 37 | PWR-HPU2 | UNKNOWN | HPU Motor #2 (M-11) β nameplate unreadable | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Checklist M-11 | Same as HPU1. | P1 | POWER |
| 38 | DECO-MTR | P-04 PF20P #3 A+/A- | Decoiler Motor (UNKNOWN NAMEPLATE) | PWR-DC | DECO-MTR | PENDING β HP unknown | PENDING β route not documented | PENDING | PENDING | TO BE VERIFIED | P2P DECO-MTR; Checklist D3 | Motor HP/V/FLA completely unknown. | P1 | POWER |
| 39 | 24V-001 | P-01 Phoenix QUINT PS 24V/30A (S/N PSB6238399) | P-01 24VDC Control Bus β field I/O | CTRL | D1-24V / D1COM (IMG_1745) | Internal bus β 24VDC bus bar | Internal panel DIN rail | 1489-A 3A breaker (confirmed) | D1-24V, D1COM terminal blocks | CONFIRMED | MER-055; IMG_1745 wire audit | Primary 24VDC supply. S/N PSB6238399. Verify output on receipt. | P1 | CONTROL |
| 40 | 24V-002 | P-01 PULS MiniLine ML30 24V | P-01 24VDC Bus (secondary/redundant) | CTRL | Internal wiring | Internal bus | DIN rail internal | None (inherent) | DIN rail output | CONFIRMED | MER-056; Checklist S2 | Secondary 24VDC. Verify load sharing with Phoenix QUINT. | P2 | CONTROL |
| 41 | 24V-003 | P-01 SOLA SDN 5-24-100C (100W) | P-01 24VDC Bus (tertiary) or dedicated load | CTRL | Internal wiring | Internal bus | DIN rail internal | 1489-A 10A (Braner panel breaker '24VDC POWER SUPPLY') | DIN rail output | CONFIRMED | MER-057; ADDENDUM Lote3 breaker bank | 100W = ~4.2A at 24V. Likely dedicated to specific load. | P2 | CONTROL |
| 42 | 24V-004 | P-01 24VDC Bus | JBOX-04 (machine side) β 24V/0V/ENA borneras | FIELD | N/A | #18 AWG control cable | P-01 β conduit β JBOX-04 | Branch protection in P-01 | 24V, 0V, ENA labels confirmed IMG_1454-1456 | CONFIRMED | IMG_1454/1456; P2P CTRL-JBF02 | Enable (ENA) signal critical for field device operation. | P2 | CONTROL |
| 43 | STO-001 | P-01 Banner ES-UA-5A Safety Relay S31/S32/S34 inputs | E-Stop pushbutton P-05 console + field E-stop stations | SAFETY | N/A | #16 AWG 2C (safety grade) | Console P-05 β conduit β P-01 Banner relay | Banner ES-UA-5A dual channel monitoring | S31/S32/S34 inputs at Banner | PARTIAL | MER-060; ADDENDUM Lote3 IMG_2157-2158 | E-stop stations and field wiring path not individually documented. | P1 | CONTROL |
| 44 | STO-002 | P-01 Banner ES-UA-5A K1/K2 Safety Outputs | P-03 Each AC890 Roll#1-#6 β STO A/STO B at X11 | SAFETY | AC890-STO | #16 AWG shielded per drive (Γ6 runs) | P-01 dedicated safety conduit β P-03 rack | Banner K1/K2; IEC 62061 SIL 2 | X11 STO A/STO B per AC890 | CONFIRMED | P2P AC890-STO; MER-060; Checklist E3 | 6 separate runs #16 AWG. Test continuity AND function. | P1 | CONTROL |
| 45 | STO-003 | P-01 Banner ES-UA-5A K1/K2 Safety Outputs | AC890PX (Flattener) STO A/STO B at X11 | SAFETY | AC890-STO-PX | #16 AWG shielded | P-01 β AC890PX cabinet | Banner K1/K2 | X11 STO A/STO B at AC890PX | CONFIRMED | P2P AC890-STO; AC890PX I/O board confirmed | Critical for 300HP flattener motor. | P1 | CONTROL |
| 46 | PLC-001 | P-01 ControlLogix 5561 / L24ER I/O | P-03 Each AC890 I/O boards X10-X15 (Tags 2301-2801) | CTRL | AC890-IO bundle | #18 AWG shielded multiconductor | P-01 β conduit β P-03 VFD rack | Drive internal | X10-X15 per drive | PARTIAL | P2P AC890-IO; IMG_1960/1962/1963/1977 | Individual conductors NOT mapped. Require tone-test at Houston. | P2 | CONTROL |
| 47 | PLC-002 | P-01 CompactLogix L24ER HSC Input A0/B0/Z0 | FSI Encoder HDE-2221-0050-QH S/N 808437 | SIG | ENC-FSI | #20 AWG shielded quad A/B/Z/GND | Leveler shaft β shielded conduit β P-01 | Drive internal / L24ER HSC | HSC A0/B0/Z0 at L24ER; encoder output | CONFIRMED | P2P ENC-FSI; MER-058 | Shield at panel end only. 50PPR. MAC E4:90:69:9C:4B:FD. | P2 | CONTROL |
| 48 | PLC-003 | P-04 PF20P #1 Encoder Input Port | UNICO Transducer 600PPR DWG 300-570 (Motor 35748) | SIG | DC-ENC-01 | #18 AWG shielded twisted pair (A/B/Z) | Motor 35748 β shielded conduit β P-04 | Drive internal | Encoder port at PF20P; transducer at motor | CONFIRMED | P2P DC-ENC-01; MER-059 | 600PPR. Shield one end. Verify connector type. | P2 | CONTROL |
| 49 | PLC-004 | P-04 PF20P #2 Encoder Input Port | UNICO Transducer 600PPR DWG 300-570 (Motor 35749) | SIG | DC-ENC-02 | #18 AWG shielded twisted pair | Motor 35749 β shielded conduit β P-04 | Drive internal | Encoder port PF20P #2; transducer motor 35749 | CONFIRMED | P2P DC-ENC-02; MER-059 | Same as DC-ENC-01. | P2 | CONTROL |
| 50 | PLC-005 | P-04 PF20P #1 Thermocouple Monitoring Input | MTR-01 UNICO 35748 Thermocouple P1/P2 (N.C./N.O.) | SIG | DC-THERMO-01 | #18 AWG shielded | Motor β shielded conduit β panel | Drive or monitoring input | Thermocouple P1/P2 at motor | PARTIAL | P2P DC-THERMO-01; MER entry | Destination terminal NOT DOCUMENTED. N.C./N.O. to confirm. | P2 | CONTROL |
| 51 | PLC-006 | P-01 terminal blocks 01xxx series | Field devices (destinations UNKNOWN) | CTRL | 01181, 01201, 01203, 01261 | #16-18 AWG | Panel internal + outgoing conduit | Panel internal breakers | Left rail terminal blocks P-01 | PARTIAL | IMG_1745 wire audit | Labels confirmed. Field destinations NOT closed. | P2 | CONTROL |
| 52 | PLC-007 | P-01 terminal blocks 5xx/7xx series | Field devices / drives (destinations UNKNOWN) | CTRL | 510,511,710,711,501,502,426,427,401,403,417,418,573,610-613 | #16-18 AWG colors pink/red/blue/gray/orange | Panel center β outgoing conduit | Panel internal protection | Center terminal blocks P-01 | PARTIAL | IMG_1745 wire audit | Highest density unresolved bundle in panel. | P2 | CONTROL |
| 53 | PLC-008 | P-01 terminal blocks ICO series | Interlock circuits β destinations UNKNOWN | CTRL | ICO53, ICO54, 0102 | #16 AWG | Panel internal + outgoing | Panel internal | Center terminal blocks P-01 | PARTIAL | IMG_1745 | SAFETY CRITICAL β ICO = interlock outputs. Verify destination AND function. | P1 | CONTROL |
| 54 | PLC-009 | P-01 PLC area terminal blocks Bxxxx | Field circuits β destinations UNKNOWN | CTRL | B1611, B1621, B3631 | #18 AWG blue | Panel lower zone | Internal panel protection | Lower terminal blocks near rack | PARTIAL | IMG panel bottom | Cross-reference with I/O assignments needed. | P2 | CONTROL |
| 55 | JBF-001 | P-01 terminal blocks | JB-FIELD-01 β Wire labels: 2561,2561A,1025,702,3161,3121,3081,M25,4025 | FIELD | 2561/2561A/1025/702/3161/3121/3081/M25/4025 | #16 AWG multiconductor pink/red/white/green | P-01 β conduit/cable tray β JB-FIELD-01 | Panel internal protection | Wire labels confirmed; panel-side terminals UNKNOWN | CONFIRMED | P2P CTRL-JBF01; Photo 47B6EC52.JPG; MER-066 | Wire labels confirmed but panel-side destinations NOT closed. Tone-test. | P1 | CONTROL |
| 56 | JBF-002 | P-01 24VDC distribution | JB-FIELD-02 β Wire labels: 24V,0V,EN,X1,X2,10A,36,157,156,1B3,1B4,215-217 | FIELD | 24V/0V/EN/X1/X2/10A/36/157/156/1B3/1B4/215-217 | #18 AWG control cable | P-01 β conduit β JB-FIELD-02 field sensor zone | 24VDC branch protection | Wire labels confirmed; EN=enable signal | CONFIRMED | P2P CTRL-JBF02; Photo 89C1F23A.JPG; MER-067 | EN (enable) signal path critical. | P1 | CONTROL |
| 57 | JBF-003 | P-01 terminal blocks (motor control) | JB102 β Terminals FWD/REV/COM/MOTOR (1-9) | FIELD | FWD/REV/COM/MOTOR (terminals 1-9) | #16 AWG colors black/white/green/pink/yellow-green | P-01 β conduit β JB102 at motor area | Panel internal protection | Terminals 1-9: FWD(1), REV(2), COM(3), MOTOR(4-9) | CONFIRMED | P2P CTRL-JB102; Photo 641C4E71.JPG; MER-065 | Inspect for corrosion from deinstallation exposure. | P2 | CONTROL |
| 58 | SOL-001 | P-01 Control Transformer 110VAC secondary | HV-REX-01 Rexroth 4WE10E33/CW110N9K4 β DIN connector | CTRL | SOL-REX | #16 AWG 2C+GND (110VAC) | P-01 transformer β conduit β hydraulic manifold | Fuse/breaker 10A on 110VAC secondary | DIN connector on valve coil | CONFIRMED | P2P SOL-REX; MER-061; Nameplate R900597186 | E33 = open center. Verify transformer tap = 110V. | P2 | CONTROL |
| 59 | SOL-002 | P-01 Control Transformer 110VAC secondary | HV-REX-02 Rexroth 4WE10E33/CW110N9K4 | CTRL | SOL-REX | #16 AWG 2C+GND | Conduit β manifold | Fuse 10A | DIN connector | PARTIAL | P2P SOL-REX; Checklist (partial visual) | Partial confirmation only. | P2 | CONTROL |
| 60 | SOL-003 | P-01 Control Transformer 110VAC secondary | HV-REX-03 Rexroth 4WE10E33/CW110N9K4 | CTRL | SOL-REX | #16 AWG 2C+GND | Conduit β manifold | Fuse 10A | DIN connector | CONFIRMED | P2P SOL-REX; Nameplate confirmed | Same as SOL-001. | P2 | CONTROL |
| 61 | SOL-004 | P-01 Control Transformer 110VAC secondary | HV-REX-04 Rexroth 4WE10J33 β DIN connector | CTRL | SOL-REX-04 | #16 AWG 2C+GND (110VAC) | Conduit β manifold | Fuse 10A | DIN connector J33 | CONFIRMED | P2P SOL-REX; Nameplate J33 confirmed | J33 = CLOSED center β different from E33. Do NOT swap. | P2 | CONTROL |
| 62 | SOL-005 | P-01 Control Transformer 120VAC secondary | HV-PARK-01 Parker D1VHW40NYCF-75 β DIN connector | CTRL | SOL-PARK | #16 AWG 2C+GND (120VAC / 5000 PSI) | Conduit β HPU manifold | Fuse 10A | DIN connector Parker valve | CONFIRMED | P2P SOL-PARK; Nameplate 120V/60Hz 5000 PSI | Requires 120V (not 110V) β separate transformer tap. | P2 | CONTROL |
| 63 | SOL-006 | P-01 Control Transformer β VOLTAGE UNKNOWN | HV-CONT-01 Continental EBA 1CN4-AC | CTRL | SOL-CONT | PENDING β voltage unknown | PENDING β location unknown | PENDING | PENDING | TO BE VERIFIED | P2P SOL-CONT; MER-064 | Voltage completely unknown. Identify valve first. | P2 | CONTROL |
| 64 | ENET-01 | P-01 Hirschmann SPIDER STX β Port TBD | ControlLogix 5561 (1756-L61) EtherNet/IP port | ENET | ENET-01 | Cat5e/6 STP RJ45 | Internal panel wiring | Switch internal | RJ45 at Hirschmann; Ethernet port at 5561 | PARTIAL | P2P ENET-01; MER-053 | IP address unknown. Assign for Houston. | P1 | NETWORK |
| 65 | ENET-02 | P-01 Hirschmann SPIDER STX β Port TBD | CompactLogix L32E (1769-L32E) EtherNet/IP port | ENET | ENET-02 | Cat5e/6 STP RJ45 | Internal panel | Switch internal | RJ45 at switch; Ethernet at L32E | PARTIAL | P2P ENET-02; MER | IP unknown. Assign for Houston. | P1 | NETWORK |
| 66 | ENET-03 | P-01 Hirschmann SPIDER STX β Port TBD | CompactLogix L24ER (MAC: E4:90:69:9C:4B:FD) | ENET | ENET-03 | Cat5e/6 STP RJ45 | Internal panel | Switch internal | RJ45 at switch; ports at L24ER | PARTIAL | P2P ENET-03; IMG_4020/4021; L24ER MAC confirmed | L24ER has dual Ethernet ports. Both TBD. IP unknown. | P1 | NETWORK |
| 67 | ENET-04 | P-01 Hirschmann SPIDER STX β Port TBD | 1794-AENT Flex I/O Adapter (label 'ETHERNET ADAPTOR') | ENET | ENET-04 | Cat5e/6 STP RJ45 | Internal panel DIN rail | Switch internal | RJ45 at switch; Ethernet at 1794-AENT | PARTIAL | P2P ENET-04; MER | IP unknown. Verify 4-5 Flex I/O modules present. | P1 | NETWORK |
| 68 | ENET-05 | P-01 Hirschmann SPIDER STX β Port TBD | VFS4-AENT (on P-04 PF20P drives) | ENET | ENET-05 (VFS4-AENT) | Cat5e/6 STP RJ45 | P-01 β conduit β P-04 drive cabinet | Switch internal | RJ45 at switch; VFS4-AENT port | PARTIAL | P2P ENET-04 VFS4-AENT; IMG_4245; MER-054 | IP unknown. | P1 | NETWORK |
| 69 | ENET-06 | P-01 Hirschmann SPIDER STX β Port TBD | PanelView Plus 600 (Cat# 2711PC-T6M20D8) β P-05 Console | ENET | ENET-06 | Cat5e/6 STP RJ45 | P-01 β conduit β P-05 operator console | Switch internal | RJ45 at switch; Ethernet at PanelView | PARTIAL | P2P ENET-06; MER; IMG_4126 | IP unknown. | P1 | NETWORK |
| 70 | ENET-07 | P-01 Hirschmann SPIDER STX β Port TBD | DirectLOGIC 205 PLC IP: 192.168.84.101 | ENET | CB-0178 / CB-1920 | Cat5e/6 STP RJ45 | P-01 Spider β cable CB-0178/CB-1920 β DL205 cabinet | Switch internal | RJ45 at switch; Ethernet at DL-205 | CONFIRMED | Reporte Forense Sec.5; IMG set 192.168.84.101; CBL labels | Only device with documented IP. | P1 | NETWORK |
| 71 | ENET-08 | P-01 Hirschmann SPIDER STX β Port TBD | PowerFlex 525 #1 (IP: 192.168.182.180) | ENET | ENET-PF525-1 | Cat5e/6 STP RJ45 | Panel β PF525 location (route unknown) | Switch internal | RJ45 at switch; Ethernet at PF525 | PARTIAL | P2P ENET-05; IP 192.168.182.180 | No nameplate on PF525 units. Machine assignment UNKNOWN. | P2 | NETWORK |
| 72 | ENET-09 | P-01 Hirschmann SPIDER STX β Port TBD | PowerFlex 525 #2 (IP: 192.168.182.118) | ENET | ENET-PF525-2 | Cat5e/6 STP RJ45 | Panel β PF525 location (route unknown) | Switch internal | RJ45 at switch; Ethernet at PF525 #2 | PARTIAL | P2P ENET-05; IP 192.168.182.118 | Same status as ENET-08. | P2 | NETWORK |
| 73 | FW-001 | AC890PX (Flattener, Node 3) FireWire port OUT | AC890 Roll#1 (Node 1, Tag 2301) FireWire port IN | FW | FIREWIRE-01 segment 1 | IEEE 1394a shielded β EXISTING MUST BE REUSED | Internal VFD rack | None (passive bus) | FireWire 6-pin connector | CONFIRMED | P2P FIREWIRE-01; MER-013 | IRREPLACEABLE. Inspect connector immediately. | P1 | NETWORK |
| 74 | FW-002 | AC890 Roll#1 (Node 1) FireWire port OUT | AC890 Roll#2 (Node 4, Tag 2401) FireWire port IN | FW | FIREWIRE-01 segment 2 | IEEE 1394a β EXISTING ONLY | Internal VFD rack | None | FireWire 6-pin | CONFIRMED | P2P FIREWIRE-01; MER-013 | Same criticality. | P1 | NETWORK |
| 75 | FW-003 | AC890 Roll#2 (Node 4) FireWire port OUT | AC890 Roll#3 (Node 5, Tag 2501) FireWire port IN | FW | FIREWIRE-01 segment 3 | IEEE 1394a β EXISTING ONLY | Internal VFD rack | None | FireWire 6-pin | CONFIRMED | P2P FIREWIRE-01; MER-013 | Sequence: Node 4 β Node 5. | P1 | NETWORK |
| 76 | FW-004 | AC890 Roll#3 (Node 5) OUT | AC890 Roll#4 (Node 6, Tag ~2601) IN | FW | FIREWIRE-01 segment 4 | IEEE 1394a β EXISTING ONLY | Internal VFD rack | None | FireWire 6-pin | CONFIRMED | P2P FIREWIRE-01; MER-013 | Node 6 assignment confirmed. | P1 | NETWORK |
| 77 | FW-005 | AC890 Roll#4 (Node 6) OUT | AC890 Roll#5 (Node 7, Tag 2701) IN | FW | FIREWIRE-01 segment 5 | IEEE 1394a β EXISTING ONLY | Internal VFD rack | None | FireWire 6-pin | CONFIRMED | P2P FIREWIRE-01; MER-013 | 903/FA option card on Roll#5. | P1 | NETWORK |
| 78 | FW-006 | AC890 Roll#5 (Node 7) OUT | AC890 Roll#6 (Node 8, Tag 2801) IN β END OF CHAIN | FW | FIREWIRE-01 segment 6 | IEEE 1394a β EXISTING ONLY | Internal VFD rack | None | FireWire 6-pin; end terminator at Node 8 | CONFIRMED | P2P FIREWIRE-01; IMG_1977; MER-013 | Node 2 is FREE/unconnected. End terminator required at Roll#6. | P1 | NETWORK |
| 79 | FD-001 | P-04 PF20P #1/#2 armature output | JBOX-01 (pass-through 500VDC on route to motors) | PWR-DC | CBL-03/04/05 | 4/0+ AWG (Red DC+, Black DCβ, Gray RTN, GrYe GND) | Drive cabinet β conduit β JBOX-01 | Drive protection | HV lugs at JBOX-01 | CONFIRMED | Reporte Forense CBL-03/04/05/06; diagrama HTML | JBOX-01 is pass-through only. 500VDC. Full LOTO. | P1 | FIELD |
| 80 | FD-002 | JBOX-01 power pass-through | JBOX-02 (TB70/TB71/TB72 β power/control separation) | PWR-DC | TB70-72 | 4/0+ AWG + control bundle | JBOX-01 β conduit β JBOX-02 (~15m subterranean) | None at JB level | TB-70, TB-71, TB-72 (confirmed labels) | CONFIRMED | P2P CKT-MTR-01; Reporte Forense; diagrama HTML | TB72 separates power from control. Critical branching point. | P1 | FIELD |
| 81 | FD-003 | JBOX-02 TB70-72 | MTR-01 UNICO S/N 35748 armature terminal box | PWR-DC | DC+ Red / DCβ Black / RTN Gray / GND GrYe | 4/0+ AWG (power); #10 AWG (field); #18 AWG (encoder/thermo) | JBOX-02 β conduit β motor terminal box (~15m) | None at JB | Motor terminal box: A1/A2, F+/F-, frame GND | CONFIRMED | diagrama rutas HTML; IMG JBOX-01/02; P2P DC-MTR-01 | GND FIRST. Connect ground before any power conductors. | P1 | FIELD |
| 82 | FD-004 | JBOX-02 TB70-72 | MTR-02 UNICO S/N 35749 armature terminal box | PWR-DC | DC+ / DCβ / RTN / GND | 4/0+ AWG | JBOX-02 β conduit β motor terminal box | None at JB | Motor terminal box A1/A2/field/GND | CONFIRMED | P2P DC-MTR-02; Reporte Forense | Same route as MTR-01. | P1 | FIELD |
| 83 | FD-005 | P-01 or field conduit | JBOX-03 (DIN rail ~20+ terminals, field control distribution) | FIELD | Multiple wires pink/red, 5+ conduits | #16-18 AWG multiconductor | 5+ conduits converge β machine structure | Panel protection | ~20+ DIN terminals | CONFIRMED | IMG_1443/1444; Reporte Forense JBOX-03 | High-density. Individual destinations NOT documented. | P2 | FIELD |
| 84 | FD-006 | P-01 24VDC distribution | JBOX-04 (24V/0V/ENA labels β machine side) | FIELD | 24V/0V/ENA | #18 AWG control | Panel β conduit β JBOX-04 machine side | Panel 24V branch protection | 2 DIN terminal strips, labels 24V/0V/ENA | CONFIRMED | IMG_1454/1456; P2P CTRL-JBF02 | ENA = enable signal for field devices. | P2 | FIELD |
| 85 | FD-007 | Machine ground bus / panel PE | JBOX-05 (ground distribution terminal box) | FIELD | GND / PE | #6 AWG green/yellow | Machine structure β ground distribution | Main ground bus | Green/yellow terminals | CONFIRMED | IMG_1460; Reporte Forense JBOX-05 | Ground FIRST. All frames bond through this point. | P1 | FIELD |
| 86 | FD-008 | P-01 or panel relay output | JBOX-06 ('DANGER' β contactors/relays above, pink/red borneras below) | FIELD | Pink/red cables | #16 AWG | Panel β conduit β JBOX-06 | Contactors/relays in JB | Borneras pink/red | CONFIRMED | IMG_1560; Reporte Forense JBOX-06 | DANGER label β may contain live voltage. Treat as energized. | P2 | FIELD |
| 87 | FD-009 | P-01 motor control output | JBOX-07 (Allen-Bradley NEMA Size 1 starter) | FIELD | Motor start/stop/run | #12 AWG estimated | Exterior machine structure | AB NEMA Size 1 integral overload | NEMA Size 1 line and load | CONFIRMED | Checklist Lote 6; Reporte Forense JBOX-07 | Motor identity UNKNOWN. Overload setting UNKNOWN. | P2 | FIELD |
| 88 | FD-010 | P-01 control output | JBOX-08 (field terminal blocks series 70) | FIELD | Series 70 numbered terminals | #16 AWG | Field area | Panel protection | Series 70 numbered borneras | CONFIRMED | Checklist Lote 6; Reporte Forense JBOX-08 | Cross-reference with wire series 7xx in panel. | P2 | FIELD |
| 89 | FD-011 | Machine leveler shaft | FSI Encoder HDE-2221-0050-QH S/N 808437 β A/B/Z | SIG | ENC-FSI | #20 AWG shielded quad | Shaft β encoder β shielded conduit β P-01 L24ER | Drive internal L24ER | Encoder terminals; L24ER HSC A0/B0/Z0 | CONFIRMED | P2P ENC-FSI; MER-058 | 50PPR. Shield single-end at panel. | P2 | FIELD |
| 90 | FD-012 | Machine structure (Γ2 locations) | Allen-Bradley 802T-AP Series J Limit Switches (Γ4+ units) | SIG | N/A | #16 AWG 2C (contact dry) | Machine structure β conduit β P-01 DI | Panel DI protection fuse | Limit switch contact; PLC DI | PARTIAL | Nameplate V2/V3 IMG_1767/IMG_1546 | 4+ units confirmed. Circuit connections NOT documented. | P2 | FIELD |
| 91 | DISC-01 | Base leveler / straightener area | DESTINATION UNKNOWN β cables cut | MIXED | NONE β no wire numbers | Red/Green/Yellow/White β cut ends | Conduit disconnected at base leveler | NONE | NONE | TO BE VERIFIED | Photo 283852BD.JPG | CRITICAL. Label EACH wire. Tone-test to identify. Replace conduit. | P1 | UNRESOLVED |
| 92 | DISC-02 | Drive train leveler area β JB open | DESTINATION UNKNOWN β JB cables pink/red | CTRL | NONE | Pink/Red cables | JB at leveler drive train | NONE | JB open | TO BE VERIFIED | Photo E4D33737.JPG | Cardan shaft separated nearby. Document JB before touching. | P2 | UNRESOLVED |
| 93 | DISC-03 | Floor level β JB severely contaminated | DESTINATION UNKNOWN | MIXED | NONE | UNKNOWN β contamination | JB at floor level contaminated area | NONE | JB contaminated | TO BE VERIFIED | Photo AA5F63A5.JPG | JB may not be reutilizable. Evaluate clean vs replace. | P1 | UNRESOLVED |
| 94 | DISC-04 | Drive train / HPU area | DESTINATION UNKNOWN β bare wire ends | MIXED | NONE | Bare wire ends | Flexible conduit disconnected | NONE | Bare ends | TO BE VERIFIED | Photo FD5AB61D.JPG | Re-terminate all bare ends. Replace conduit flex. | P2 | UNRESOLVED |
| 95 | DISC-05 | Base HPU β JB open | Motor visible β nameplate NOT readable | MIXED | NONE | UNKNOWN | JB at HPU base | NONE | JB open | TO BE VERIFIED | Photo 3BFD6EAC.JPG | Photograph motor nameplate FIRST. | P2 | UNRESOLVED |
| 96 | DISC-06 | Floor in front of MCC / main panel | DESTINATION UNKNOWN β mass of cut cables | MIXED | NONE | Pink/Red AND Blue cables β cut mass | In front of MCC area | NONE | Multiple cables loose | TO BE VERIFIED | Photo IMG-NEW-02 | CRITICAL. Multiple control circuits. Tone-test EVERY conductor. | P1 | UNRESOLVED |
| 97 | DISC-07 | Field area β possible thermal damage | DESTINATION UNKNOWN | MIXED | NONE | UNKNOWN β possible carbonization | Field area | NONE | Possible thermal damage | TO BE VERIFIED | Forensic notes | If carbonized: REPLACE entire cable β do NOT re-terminate. | P2 | UNRESOLVED |
| 98 | DISC-08 | Auxiliary panel area | DESTINATION UNKNOWN β bare copper | MIXED | NONE | Pink cable + BARE COPPER | Auxiliary panel | NONE | Bare copper β short circuit risk | TO BE VERIFIED | Forensic notes | IMMEDIATE: Insulate bare copper before transport. | P2 | UNRESOLVED |
| 99 | PWR-MARA100 | UNKNOWN | Marathon 100HP Inv.Duty 460V | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Drive/starter, route, protection all UNKNOWN. | P1 | UNRESOLVED |
| 100 | PWR-MARA60 | UNKNOWN | Marathon 60HP Inv.Duty 460V | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Same status. | P1 | UNRESOLVED |
| 101 | PWR-WEG125 | UNKNOWN | WEG 125HP 460V 1780RPM | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Same status. | P1 | UNRESOLVED |
| 102 | PWR-TECO10A | UNKNOWN | TECO Westinghouse MAX-PE 10HP #1 | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Same status. | P2 | UNRESOLVED |
| 103 | PWR-TECO10B | UNKNOWN | TECO Westinghouse MAX-PE 10HP #2 | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Same status. | P2 | UNRESOLVED |
| 104 | PWR-WEG10 | UNKNOWN | WEG 10HP 208-230/460V | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Same status. | P2 | UNRESOLVED |
| 105 | PWR-BALDOR15 | UNKNOWN | Baldor Super-E 1.5HP Marine Duty 56C | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Cat# 61C4900C1AR confirmed | Same status. IEEE-45. | P2 | UNRESOLVED |
| 106 | PWR-MARA4 | UNKNOWN | Marathon 4HP 208-230/460V | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Motor nameplate confirmed | Same status. | P2 | UNRESOLVED |
| 107 | PWR-HPU1 | UNKNOWN | HPU Motor #1 (M-10) β nameplate unreadable | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Checklist M-10 | HPU may auto-start. LOTO. | P1 | UNRESOLVED |
| 108 | PWR-HPU2 | UNKNOWN | HPU Motor #2 (M-11) β nameplate unreadable | PWR-AC | UNKNOWN | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Checklist M-11 | Same as HPU1. | P1 | UNRESOLVED |
| 109 | PWR-DECO | P-04 PF20P #3 (Decoiler) | Decoiler motor β HP/V/FLA/Frame COMPLETELY UNKNOWN | PWR-DC | DECO-MTR | PENDING | NOT DOCUMENTED | PENDING | NOT DOCUMENTED | TO BE VERIFIED | Drive confirmed; IMG_1537 | Motor nameplate MUST be photographed at Houston. | P1 | UNRESOLVED |
| 110 | PWR-ROLL-ALL | P-03 AC890 Nodes 1/4/5/6/7/8 | Roll Motors #1-#6 β motor nameplates PENDING | PWR-AC | Tags 2301/2401/2501/~2601/2701/2801 | HP from drives: 75/100/75/25/25/25 HP | VFD rack β conduit β roll motors | Drive integral protection | U/V/W drive; T1/T2/T3 motor | PARTIAL | P2P ROLL-01 to ROLL-06; MER-005 to MER-010 | Motor nameplate FLA not confirmed β cable sizes are estimates. | P1 | UNRESOLVED |