Matriz de Tableros

Conexiones panel a panel β€” 17 registros.

# FROM PANEL TO PANEL CIRCUIT IDs CONNECTION TYPE CABLE COUNT CABLE SPEC SUMMARY ROUTE STATUS SUMMARY CRITICAL NOTES
1 P-02 (MCC) P-01 (Main Panel) SU-002 PWR-AC 1 circuit (L1/L2/L3+GND) 3/0 AWG+ XHHW-2 MCC to P-01 top entry β€” cable tray WARNING MCC NOT DESIGNED. Entire line blocked until utility service and MCC engineering completed.
2 P-02 (MCC) P-04 (DC Drives) DC-PWR-01, DC-PWR-02, DC-PWR-03 PWR-AC 3 circuits (3Γ— L1/L2/L3) 2/0 AWG XHHW-2 per circuit MCC β†’ cable tray β†’ P-04 PARTIAL Dedicated breakers ~400A each (pending MCC design). DC-PWR-03 (Decoiler) motor HP completely unknown.
3 P-02 (MCC) P-03 (AC890 Rack) SU-010, AC890-PWR-RACK PWR-AC 1 circuit through TCI reactors 250A+ estimated MCC β†’ cable tray β†’ P-03 through TCI KDRH3L/KDRF2L PARTIAL Rack input breaker PENDING. FLA input for rack not calculated.
4 P-02 (MCC) AC890PX SU-011, AC-PWR-PX PWR-AC 1 circuit ~250 MCM estimated MCC β†’ cable tray β†’ AC890PX standalone PARTIAL Dedicated breaker size PENDING Parker manual.
5 P-01 (Main Panel) P-04 (DC Drives) SU-004, SU-005 (via P-01 bus) PWR-AC 2 circuits (pass-through from MCC bus) 2/0 AWG XHHW-2 P-01 to P-04 β€” cable tray CONFIRMED Input: 460V/336.6A 3PH each. Output: 500VDC/412A REGEN.
6 P-01 (Main Panel) P-03 (AC890 Rack) STO-002, PLC-001, AC890-IO SAFETY + CTRL STO: 6 runs #16 AWG + I/O bundle #16 AWG shielded (STO); #18 AWG multiconductor (I/O) P-01 dedicated safety conduit β†’ P-03 PARTIAL STO FIRST function test before any motor. I/O individual conductors NOT mapped.
7 P-01 (Main Panel) AC890PX STO-003, AC890-STO-PX SAFETY 1 run STO A/STO B #16 AWG shielded P-01 β†’ AC890PX cabinet CONFIRMED Critical for 300HP flattener motor.
8 P-01 (Main Panel) P-05 (Console) STO-001, ENET-06 SAFETY + ENET 1 E-stop circuit + 1 Ethernet cable #16 AWG 2C safety + Cat5e/6 STP P-01 β†’ conduit β†’ P-05 PARTIAL E-stop field wiring path not individually documented. PanelView IP unknown.
9 P-01 (Main Panel) DL-205 ENET-07 ENET 1 Ethernet cable (CB-0178/CB-1920) Cat5e/6 STP RJ45 P-01 Spider β†’ cable β†’ DL205 cabinet CONFIRMED IP 192.168.84.101 CONFIRMED. Only device with documented IP.
10 P-01 (Main Panel) PF525 #1/#2 ENET-08, ENET-09 ENET 2 Ethernet cables Cat5e/6 STP RJ45 Panel β†’ PF525 locations (route unknown) PARTIAL IPs 192.168.182.180 and .118 documented. Machine assignment UNKNOWN.
11 P-04 (DC Drives) MTR-01 (UNICO S/N 35748) DC-MTR-01, DC-FLD-01, DC-ENC-01, DC-THERMO-01 PWR-DC + SIG 4 circuits: armature + field + encoder + thermocouple 4/0 AWG (arm), #10 AWG (field), #18 AWG (enc/thermo) P-04 β†’ conduit β†’ pit β†’ JBOX-01 β†’ JBOX-02 TB70-72 β†’ Motor PARTIAL DO NOT invert polarity A1/A2. Measure field resistance 11.3 ohm.
12 P-04 (DC Drives) MTR-02 (UNICO S/N 35749) DC-MTR-02, DC-FLD-02, DC-ENC-02 PWR-DC + SIG 3 circuits: armature + field + encoder 4/0 AWG + #10 AWG + #18 AWG Same route as MTR-01 CONFIRMED Parallel field mode: 150V/5.5A.
13 P-03 (AC890 Rack) Roll Motors #1-#6 ROLL-01 to ROLL-06 PWR-AC 6 motor circuits #4 to #10 AWG per motor HP VFD rack β†’ conduit β†’ each roll motor PARTIAL Motor nameplates PENDING. HP from drive tags only. Cable sizes estimated.
14 AC890PX MTR-300 (Flattener 300HP) AC-MTR-300, SU-012 PWR-AC 1 motor circuit (U/V/W) 350 MCM per phase (355A FLA) AC890PX β†’ conduit β†’ pit β†’ motor CONFIRMED BASE FREQ = 84Hz NOT 60Hz. DPFV blower MANDATORY.
15 P-03 (AC890 Rack) Internal FireWire Chain FW-001 to FW-006 FW 6 daisy-chain segments IEEE 1394a shielded β€” IRREPLACEABLE Internal VFD rack CONFIRMED Node sequence MANDATORY: PX(3)β†’1β†’4β†’5β†’6β†’7β†’8. DO NOT modify.
16 P-01 (Main Panel) JBOX-01 to JBOX-08 FD-001 to FD-010, JBF-001 to JBF-003 FIELD + CTRL 10+ field circuits #12-18 AWG various P-01 β†’ conduit β†’ field JBOXes PARTIAL JBOX-05 = ground distribution (FIRST). JBOX-06 = DANGER label. JBOX-03 high-density.
17 P-01 (Main Panel) Solenoid Valves SOL-001 to SOL-006 CTRL 6 solenoid circuits (110/120VAC) #16 AWG 2C+GND P-01 transformer β†’ conduit β†’ hydraulic manifold PARTIAL E33 β‰  J33 (open vs closed center). Parker requires 120V not 110V. Continental voltage UNKNOWN.